Find the minimum lumber size for any beam or header span and load condition. Covers dimensional lumber, LVL, and glulam beams for doors, windows, and structural openings.
Enter your beam span, the tributary width it supports, the load type, and lumber species. The calculator returns the minimum member size based on bending stress (Fb), the required section modulus, and the total load. Always verify with your local building code span tables or a structural engineer, this tool is for planning and comparison, not final specification.
Beam sizing is governed by bending stress. The key formula: required section modulus S = M ÷ Fb, where M is the maximum bending moment (wL²÷8 for a uniformly loaded simple span in inch-pounds) and Fb is the lumber's allowable bending stress. A larger S value means the beam can resist more bending, deeper and wider members have higher S values.
Worked example: an 8 ft beam supporting a floor (50 psf) with a 6 ft tributary width, 1 story, Southern Pine #2 (Fb = 1,000 psi). Load per linear foot = 50 × 6 = 300 plf. Total load = 300 × 8 = 2,400 lbs. Maximum moment = 300 × 8² ÷ 8 = 2,400 ft-lbs = 28,800 in-lbs. Required S = 28,800 ÷ 1,000 = 28.8 in³. A doubled 2×10 (S = 42.78 in³) is the minimum size that works. A single 2×12 (S = 31.64 in³) also works and may be more practical.
| Opening Width | 1 Story Above | 2 Stories Above | Notes |
|---|---|---|---|
| Up to 3 ft | (2) 2×4 | (2) 2×6 | Non-load-bearing: (2) 2×4 always OK |
| 3–4 ft | (2) 2×6 | (2) 2×8 | Standard door opening |
| 4–6 ft | (2) 2×8 | (2) 2×10 | Sliding door, large window |
| 6–8 ft | (2) 2×10 | (2) 2×12 | Wide opening, garage door |
| 8–10 ft | (2) 2×12 | LVL required | Large garage, folding door |
| 10–12 ft | LVL or engineer | Engineer required | Always verify with engineer |
| Over 12 ft | Engineer required | Engineer required | LVL, glulam, or steel |
| Species / Product | Fb (psi) | Relative Strength | Notes |
|---|---|---|---|
| SPF #2 | 800 | Baseline | Common in Northeast and Canada |
| Hem-Fir #2 | 900 | +12% | West Coast; moderate availability |
| Southern Pine #2 | 1,000 | +25% | Southeast; very common |
| Douglas Fir-Larch #2 | 1,200 | +50% | Strongest dimensional lumber; West Coast |
| Glulam 24F | 2,400 | 3× dimensional | Large spans; custom depths |
| LVL 1.9E | 2,600 | 3.25× dimensional | Most common engineered option |
Headers are short beams over doors and windows, typically spanning 3–12 feet and carrying one floor or roof above. For non-load-bearing walls, a doubled 2×4 flat header is usually sufficient. For load-bearing walls, use this calculator with the actual span and tributary width. Standard residential headers are doubled 2×10 or 2×12 with a 1/2" plywood spacer to match the 3.5" wall thickness.
LVL (laminated veneer lumber) has an Fb of 2,600 psi, roughly 2.5–3× stronger than dimensional lumber of the same cross-section. This means an LVL can often replace a much larger solid timber. A single 3.5×9.5" LVL has a section modulus of about 53 in³, equivalent to a tripled 2×10 in dimensional lumber. LVL doesn't warp, shrink, or split and is the standard for large spans in modern residential construction.
Understanding what "span" and "tributary width" actually mean in physical terms is the most important step before using this calculator. The diagram below shows a typical floor beam installation and the measurements this calculator uses.
The load type you select has a significant impact on the required beam size, sometimes the difference of two lumber sizes. Here's what each load type means and when to use it:
| Load Type | Design Load | When to Use | Notes |
|---|---|---|---|
| Roof, snow country | 50 psf total | Areas with significant snowfall (most of northern US) | Includes 30 psf live (snow) + 20 psf dead (roofing materials, framing) |
| Roof, no snow | 30 psf total | Southern states, mild climates | 20 psf live + 10 psf dead; check local code for actual ground snow load |
| Floor | 50 psf total | Residential floor beams | 40 psf live (occupancy) + 10 psf dead (flooring, subfloor, joists); most common residential floor load |
| Deck | 60 psf total | Exterior deck beams | 40 psf live + 20 psf dead; decks use higher dead load than interior floors per IRC |
| Door/Window header | 40 psf total | Headers over openings in load-bearing walls | Combined roof and floor loads for typical one-story tributary; use higher load types for headers under heavy loads |
These are simplified design loads for residential construction. Your local building code may specify different values based on ground snow load (Pg), wind exposure, and occupancy. For anything outside standard residential use, commercial, industrial, unusually high loads, consult your local code or a structural engineer.
Dimensional lumber beams, doubled or tripled 2× members, are the most common choice for residential headers and short-span floor beams. They're available at any lumber yard, easy to cut and install, and work well for spans up to 10–12 feet depending on load. The main limitation is bending strength: the maximum Fb for Douglas Fir #2 is 1,200 psi, which means even large dimensional members hit their limits on longer spans or heavier loads.
One detail that matters: a doubled 2×10 is not the same as a 4×10. A true 4×10 has a section modulus of 49.9 in³. A doubled 2×10 (two separate pieces nailed together) has an effective section modulus of 42.78 in³, about 14% less, because the two pieces can slip slightly relative to each other under load. The benefit of doubled members is that they match standard 3.5-inch wall framing without a spacer.
Laminated Veneer Lumber (LVL) is the default engineered lumber choice for spans over 10 feet and loads that exceed what dimensional lumber can handle economically. With an Fb of 2,600 psi, more than twice Douglas Fir #2, a single LVL can often replace a tripled or quadrupled dimensional lumber beam. LVL is also dimensionally stable: it won't warp, crown, or shrink after installation, which matters for finished surfaces and long-term performance.
LVL is sold in 1.75-inch-wide plies that are typically doubled or tripled. A 3.5-inch-wide double LVL (two 1.75" plies) fits a standard 3.5-inch stud wall, a common configuration for residential headers. A 3.5×9.5" double LVL has a section modulus of about 52.6 in³, significantly stronger than a doubled 2×10 (42.78 in³) of the same rough width. Common depths run from 7.25" through 18" in standard increments.
Glue-laminated timber (glulam) is used for long spans, architectural exposed beams, and situations where a single large timber section is desired aesthetically. Standard residential glulam uses a 24F designation (Fb = 2,400 psi) and is available in depths from 6" to 30" or more. Glulam is the right choice for spans exceeding 20 feet, ridge beams in cathedral ceiling applications, and any exposed structural element where appearance matters.
| Application | Typical Span | Load | Trib. Width | Recommended Size |
|---|---|---|---|---|
| Standard door header (interior) | 3 ft | Floor 50 psf | 4 ft | (2) 2×6 SP #2 |
| Standard door header (exterior, 1 story) | 3 ft | Roof 30 psf | 6 ft | (2) 2×6 DF #2 |
| Sliding door / large window | 6 ft | Floor 50 psf | 6 ft | (2) 2×10 SP #2 |
| Garage door header (16 ft) | 16 ft | Roof 30 psf | 6 ft | LVL 3.5×11.25 or engineer |
| Flush floor beam (open plan) | 12 ft | Floor 50 psf | 8 ft | LVL 3.5×11.25 or (3) 2×12 DF |
| Ridge beam (cathedral ceiling) | 20 ft | Roof 50 psf | 10 ft | Glulam 5.125×16.5 or engineer |
| Deck beam (ground level) | 10 ft | Deck 60 psf | 7 ft | (3) 2×10 PT SP or LVL |
This calculator handles standard residential beam sizing for planning purposes. There are specific situations where a licensed structural engineer (PE) must review and stamp the design before permits will be issued, and situations where you genuinely need professional input regardless of permit requirements.
Most permitted structural work in the US requires engineer-stamped drawings anyway, your building department will tell you if this applies to your project. Budget $500–$2,000 for a structural engineer's involvement on a residential beam or header project, depending on complexity.