Reviewed and updated: August 2026
Calculate flue liner size, chimney brick count, mortar, and required chimney height for any fireplace opening or wood stove. Includes IRC 2-3-10 height and clearance rules.
The flue must be sized to at least 1/10 of the fireplace opening area (or 1/12 for round flues). Enter your fireplace opening dimensions.
IRC 2-3-10 rule: chimney must extend 3 ft above roof penetration and 2 ft above any part of the building within 10 ft horizontally.
This calculator covers three chimney planning needs: sizing the flue liner based on your fireplace opening (Flue Size tab), estimating bricks, mortar, and flue tile sections for the above-roof chimney section (Brick Count tab), and checking IRC height clearance requirements based on your roof pitch and chimney location (Height Rules tab).
The flue cross-sectional area must equal at least 1/10 of the fireplace opening area for rectangular clay tile flues, or 1/12 for round metal flues. A larger flue is better than a smaller one, oversizing by 10–20% improves draft. Undersizing causes smoke spillage into the room.
Worked example: a 36×28 inch fireplace opening has an area of 1,008 sq in. Minimum flue area = 1,008 ÷ 10 = 100.8 sq in. A standard 12×12 inch clay flue tile has an actual inside area of approximately 113 sq in, the smallest standard size that meets this requirement. An 8×12 inch tile (actual ~75 sq in) would be undersized for this opening.
| Flue Liner | Actual Inside Area | Max Fireplace Opening | Typical Application |
|---|---|---|---|
| 8" × 8" | ~50 sq in | 500 sq in (e.g. 24"×20") | Small fireplace or wood stove |
| 8" × 12" | ~70–77 sq in | 750 sq in (e.g. 30"×25") | Small to medium fireplace |
| 12" × 12" | ~113 sq in | 1,130 sq in (e.g. 36"×31") | Standard 36" fireplace |
| 13" × 13" | ~127 sq in | 1,270 sq in (e.g. 40"×31") | Medium-large fireplace |
| 13" × 17" | ~162 sq in | 1,620 sq in (e.g. 48"×33") | Large fireplace opening |
| 17" × 17" | ~216 sq in | 2,160 sq in (e.g. 60"×36") | Very large or double-sided |
| 8" round | ~50 sq in | 600 sq in (1/12 rule) | Small metal liner for gas |
| 10" round | ~78 sq in | 936 sq in (1/12 rule) | Medium gas or wood stove |
| 12" round | ~113 sq in | 1,356 sq in (1/12 rule) | Larger gas or oil appliance |
The IRC requires two conditions both be met: the chimney cap must extend at least 3 ft above the point where the chimney exits the roof, and it must extend at least 2 ft above any part of the roof structure within 10 ft horizontally. Whichever measurement produces the taller chimney governs.
On a 6/12 pitch roof with the chimney 8 ft from the ridge: the rise at 10 ft from the chimney toward the ridge = 10 × (6/12) = 5 ft. Minimum height = max(3, 2 + 5) = 7 ft above the roof penetration. On a flat or low-pitch roof near the center, the 3 ft minimum usually governs and the chimney only needs to clear that threshold.
| Component | Standard Specification | Notes |
|---|---|---|
| Chimney brick | Hard-fired face brick, SW grade | SW = severe weathering; required in freeze-thaw climates |
| Mortar (joints) | Type S, 3/8" joints | Never use Type N on exterior chimney |
| Flue liner (new) | ASTM C315 clay tile | Standard 2 ft sections; sold at masonry suppliers |
| Flue liner (retrofit) | 316L stainless flexible liner | For wood; use 304 SS for gas and oil |
| Chimney cap | Cast stone or precast concrete | Extends 2–4" beyond chimney on all sides to shed water |
| Flashing | Step + counter flashing, 26-gauge lead or copper | Most critical waterproofing detail, do not use aluminum |
The diagram below shows the 2-3-10 rule that governs chimney height above the roofline. This rule applies to all fuel-burning appliances vented through a masonry chimney under IRC R1003.9.
2-3-10 rule per IRC R1003.9 · 3 ft above roof penetration · 2 ft above any structure within 10 ft horizontal
Draft is the negative pressure that pulls combustion gases up and out of the chimney. Adequate draft requires the right combination of flue size, chimney height, and temperature differential. A chimney that is too short, too large, or in poor thermal condition will backdraft, pushing smoke into the room instead of exhausting it.
| Factor | Effect on Draft | Practical Note |
|---|---|---|
| Chimney height | Taller = stronger draft | Minimum 15 ft total height from firebox to cap; 20+ ft preferred for wood-burning |
| Flue area | Correct size = optimal draft; oversized = weak draft | 1/10 rule minimum for rectangular, 1/12 for round; oversizing by 10% is fine |
| Flue temperature | Hotter = stronger draft | Cold flues cause startup smoke; preheat with paper before lighting |
| Negative house pressure | Tightly sealed houses resist draft | Open a window slightly if persistent backdraft occurs in tight homes |
| Wind | Downdraft on lee side of roof | Chimney cap with wind collar recommended where prevailing wind is an issue |
| Obstructions | Trees, additions within 10 ft can cause downdraft | Observe the 2-3-10 rule; cap type matters near obstructions |
The flue liner is the interior conduit that channels combustion gases from the appliance to the outside. It must be matched to the fuel type and appliance being vented. Using the wrong liner type is a serious fire hazard and building code violation.
| Liner Type | Fuel Types | Lifespan | Notes |
|---|---|---|---|
| Clay tile (standard) | Wood, oil, coal | 50+ years if maintained | Most common; must be intact, cracked tiles allow combustion gases into masonry and framing |
| Cast-in-place (poured) | All fuel types | 50+ years | Best for relining irregular or deteriorated chimneys; creates seamless liner |
| Stainless steel flexible | Gas, oil, wood pellets | 15–25 years | Common for relining; must match liner alloy to fuel type (AL29-4C for gas, 316L for oil/wood) |
| Rigid stainless | Gas, oil | 25+ years | Better than flexible but requires straight chimney sections |
| Aluminum flexible | Gas only (Category I) | 15–20 years | Least expensive; only approved for non-positive pressure gas appliances |
The National Fire Protection Association (NFPA 211) and most building codes require annual chimney inspection. Creosote buildup in wood-burning chimneys is a leading cause of house fires. Here is the standard maintenance schedule:
| Task | Frequency | Who Does It |
|---|---|---|
| Visual inspection | Annually (spring or fall) | Certified chimney sweep (CSIA) |
| Cleaning (wood-burning) | When creosote reaches 1/8" | Certified chimney sweep |
| Gas appliance inspection | Annually | Certified sweep or HVAC technician |
| Cap and crown inspection | Every 2–3 years | Sweep or mason |
| Tuckpointing (mortar joints) | When cracking or spalling visible | Masonry contractor |
| Waterproofing | Every 5–7 years | Sweep or mason |
| Full Level 2 inspection | Before purchase, after fire or earthquake | CSIA-certified sweep with camera |